CVE-2025-3498
Radiflow iSAP Smart Collector Unauthenticated Remote Command Execution and Configuration Modification
Description
An unauthenticated user with management network access can get and modify the Radiflow iSAP Smart Collector (CentOS 7 - VSAP 1.20) configuration. The device has two web servers that expose unauthenticated REST APIs on the management network (TCP ports 8084 and 8086). An attacker can use these APIs to get access to all system settings, modify the configuration and execute some commands (e.g., system reboot).
INFO
Published Date :
July 9, 2025, 9:15 a.m.
Last Modified :
July 10, 2025, 1:17 p.m.
Source :
a6d3dc9e-0591-4a13-bce7-0f5b31ff6158
Remotely Exploitable :
Yes !
Impact Score :
5.3
Exploitability Score :
3.9
Affected Products
The following products are affected by CVE-2025-3498
vulnerability.
Even if cvefeed.io
is aware of the exact versions of the
products
that
are
affected, the information is not represented in the table below.
No affected product recoded yet
References to Advisories, Solutions, and Tools
Here, you will find a curated list of external links that provide in-depth
information, practical solutions, and valuable tools related to
CVE-2025-3498
.
URL | Resource |
---|---|
https://www.cvcn.gov.it/cvcn/cve/CVE-2025-3498 |
We scan GitHub repositories to detect new proof-of-concept exploits. Following list is a collection of public exploits and proof-of-concepts, which have been published on GitHub (sorted by the most recently updated).
Results are limited to the first 15 repositories due to potential performance issues.
The following list is the news that have been mention
CVE-2025-3498
vulnerability anywhere in the article.
The following table lists the changes that have been made to the
CVE-2025-3498
vulnerability over time.
Vulnerability history details can be useful for understanding the evolution of a vulnerability, and for identifying the most recent changes that may impact the vulnerability's severity, exploitability, or other characteristics.
-
New CVE Received by a6d3dc9e-0591-4a13-bce7-0f5b31ff6158
Jul. 09, 2025
Action Type Old Value New Value Added Description An unauthenticated user with management network access can get and modify the Radiflow iSAP Smart Collector (CentOS 7 - VSAP 1.20) configuration. The device has two web servers that expose unauthenticated REST APIs on the management network (TCP ports 8084 and 8086). An attacker can use these APIs to get access to all system settings, modify the configuration and execute some commands (e.g., system reboot). Added CVSS V3.1 AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:H/A:L Added CWE CWE-306 Added Reference https://www.cvcn.gov.it/cvcn/cve/CVE-2025-3498
CWE - Common Weakness Enumeration
While CVE identifies
specific instances of vulnerabilities, CWE categorizes the common flaws or
weaknesses that can lead to vulnerabilities. CVE-2025-3498
is
associated with the following CWEs:
Common Attack Pattern Enumeration and Classification (CAPEC)
Common Attack Pattern Enumeration and Classification
(CAPEC)
stores attack patterns, which are descriptions of the common attributes and
approaches employed by adversaries to exploit the CVE-2025-3498
weaknesses.