10.0
CRITICAL CVSS 4.0
CVE-2026-3611
Honeywell IQ4x BMS Controller Missing authentication for critical function
Description

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

INFO

Published Date :

March 12, 2026, 9:16 p.m.

Last Modified :

March 12, 2026, 9:16 p.m.

Remotely Exploit :

Yes !
Affected Products

The following products are affected by CVE-2026-3611 vulnerability. Even if cvefeed.io is aware of the exact versions of the products that are affected, the information is not represented in the table below.

No affected product recoded yet

CVSS Scores
The Common Vulnerability Scoring System is a standardized framework for assessing the severity of vulnerabilities in software and systems. We collect and displays CVSS scores from various sources for each CVE.
Score Version Severity Vector Exploitability Score Impact Score Source
CVSS 3.1 CRITICAL 7d14cffa-0d7d-4270-9dc0-52cabd5a23a6
CVSS 3.1 CRITICAL [email protected]
CVSS 4.0 CRITICAL 7d14cffa-0d7d-4270-9dc0-52cabd5a23a6
CVSS 4.0 CRITICAL [email protected]
Solution
Remediate authentication bypass by enabling and configuring user accounts.
  • Ensure user accounts are created and enabled.
  • Disable direct HTTP access to HMI.
  • Change default credentials immediately.
  • Apply vendor-provided security updates.
References to Advisories, Solutions, and Tools

Here, you will find a curated list of external links that provide in-depth information, practical solutions, and valuable tools related to CVE-2026-3611.

URL Resource
https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-069-03.json
https://www.cisa.gov/news-events/ics-advisories/icsa-26-069-03
https://www.honeywell.com/us/en/contact
CWE - Common Weakness Enumeration

While CVE identifies specific instances of vulnerabilities, CWE categorizes the common flaws or weaknesses that can lead to vulnerabilities. CVE-2026-3611 is associated with the following CWEs:

Common Attack Pattern Enumeration and Classification (CAPEC)

We scan GitHub repositories to detect new proof-of-concept exploits. Following list is a collection of public exploits and proof-of-concepts, which have been published on GitHub (sorted by the most recently updated).

Results are limited to the first 15 repositories due to potential performance issues.

The following list is the news that have been mention CVE-2026-3611 vulnerability anywhere in the article.

The following table lists the changes that have been made to the CVE-2026-3611 vulnerability over time.

Vulnerability history details can be useful for understanding the evolution of a vulnerability, and for identifying the most recent changes that may impact the vulnerability's severity, exploitability, or other characteristics.

  • New CVE Received by [email protected]

    Mar. 12, 2026

    Action Type Old Value New Value
    Added Description The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
    Added CVSS V4.0 AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
    Added CVSS V3.1 AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
    Added CWE CWE-306
    Added Reference https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-069-03.json
    Added Reference https://www.cisa.gov/news-events/ics-advisories/icsa-26-069-03
    Added Reference https://www.honeywell.com/us/en/contact
EPSS is a daily estimate of the probability of exploitation activity being observed over the next 30 days. Following chart shows the EPSS score history of the vulnerability.
Vulnerability Scoring Details
Base CVSS Score: 10
Attack Vector
Attack Complexity
Attack Requirements
Privileges Required
User Interaction
VS Confidentiality
VS Integrity
VS Availability
SS Confidentiality
SS Integrity
SS Availability
Base CVSS Score: 10
Attack Vector
Attack Complexity
Privileges Required
User Interaction
Scope
Confidentiality Impact
Integrity Impact
Availability Impact